Firstly ,Fan Coil Unit Controller With Modbus (ASHV60AR) 100-240VAC, R485 Communication, Pipe fan coil temperature controller, HVAC
Secondly,Introduction:ASHV60AR has three working mode: cooling, heating and ventilation. Also make use of super robust MCU, and excellent components, with simple and easy interactivity. The controller suits for zones temperature control of central air conditioning.
Main Function:
working mode: cooling, heating and ventilation.
Low temperature protection function.
Sensor fault warning.
Auto restart function.
Keypad Lock.
RS485 function.
Technical Specification:
Sensor: NTC, control accuracy:±1°C
Celsius temperature set range:5~35°C
Celsius temperature display range:-9~50°C
Working environments: 0~45°C, 5~95% RH(without dew)
Power supply: AC 100~240V, 50/60HZ. Power consumption: < 2W
Load limitation: 1A with resistive load
Dimension: 86x86x12 mm
Installation: 60mm standard
R485 Communication function:
Connected with RS485 ports on controller, follow Modbus-Rtu protocol to remote control system.
Method: Serial, Asynchronous, Half-duplex
Baud Rate:2400,4800,9600,19200 can be set
Data length: 8(LSB front)
Parity Check: no
Start bit: 1
Stop bit: 1
One piece packing: 11 * 9 * 7.5 cm, 0.251 kg
One carton packing: 33 * 37 * 47 cm, 17.1 kg, 64 pcs